NAPP2233347811 2022 MAJOR I FLAR @ 0

General Incident Information

[fAPP2126032949] TALCO CTB
[372043] TAP ROCK OPERATING, LLC
Inactive
Amended C-129 Accepted, Operator required to follow Monthly/Annual Waste Rule reporting requirements
Flare

C-16-26S-35E      308 FNL      1490 FWL
32.04972,-103.376993 NAD83
Hobbs
Lea (25)


Severity Indicators














Notes

Industry Rep


Contact Details


Event Dates

11/28/2022
12:01 AM

11/28/2022
11:59 PM
12/13/2022

 

Incident Dates

19.15.29 NMAC - RELEASES

Type Action Received Denied Approved
Initial C-129 Report [162166] 12/13/2022 12/13/2022
Notification [162160] 11/29/2022 11/29/2022

19.15.30 NMAC - REMEDIATION

Type Action Received Denied Approved

Compositional Analysis of Vented and/or Flared Natural Gas

Date Methane
(CH4) %
Nitrogen
(N2) %
Hydrogen Suffide
(H2S) PPM
Carbon Dioxide
(CO2) %
Oxygen
(O2) %
Natural Gas Analysis 12/13/2022 68 1 0 0 0

Incident Materials

Cause Source Material Volume Units
Unk. Released Recovered Lost
Equipment Failure Gas Compressor Station Natural Gas Flared 595 0 595 Mcf
 
The concentration of dissolved chloride in the produced water >10,000 mg/l:           Yes           No        

Incident Events

Date Detail
12/13/2022 Corrective actions provided by the operator: MP flare volume high due to high sales gas line pressure (Lucid) and our two small VRUs not being strong enough to buck the high line pressure. Big unit is not moving the volume it should be moving. The LP flare volume was high due tank vent blower sending tank vapors to an already packed and over pressured MP system which causes the LP system to back up and have to route to flare.
12/13/2022 Steps taken to prevent waste provided by the operator: MP flare volume high due to high sales gas line pressure (Lucid) and our two small VRUs not being strong enough to buck the high line pressure. Big unit is not moving the volume it should be moving. The LP flare volume was high due tank vent blower sending tank vapors to an already packed and over pressured MP system which causes the LP system to back up and have to route to flare.
12/13/2022 Incident updated by the operator, upon the submission of a amendment for flaring of natural gas report.
11/29/2022 The (12/13/2022, C-129A) application [162166] was assigned to this incident.
11/29/2022 The (11/29/2022, NOMVF) application [162160] was assigned to this incident.
11/29/2022 New incident created by the operator, upon the submission of a notification of venting or flaring.
11/28/2022 The event discovered by the operator; will be tracked as a Flare till submission of the required subsequent C-129A.