NAPP2531153328 2025 MAJOR AAA VENT @ FAPP2123052765

General Incident Information

[fAPP2123052765] HARVEST FOUR CORNERS GATHER SYSTEM
[373888] Harvest Four Corners, LLC
Inactive
Amended C-129 Accepted, Operator required to follow Monthly/Annual Waste Rule reporting requirements
Vent

M-34-32N-07W      0 FNL      0 FEL
36.93142,-107.56029 NAD83
Aztec
San Juan (45)


Severity Indicators














Notes

Industry Rep
Referred to Environmental Inspector


Contact Details


Event Dates

11/06/2025
06:10 PM

11/06/2025
07:03 PM
11/21/2025

 

Incident Dates

19.15.29 NMAC - RELEASES

Type Action Received Denied Approved
Initial C-129 Report [527046] 11/17/2025 11/17/2025
Notification [524541] 11/07/2025 11/07/2025

19.15.30 NMAC - REMEDIATION

Type Action Received Denied Approved

Compositional Analysis of Vented and/or Flared Natural Gas

Date Methane
(CH4) %
Nitrogen
(N2) %
Hydrogen Suffide
(H2S) PPM
Carbon Dioxide
(CO2) %
Oxygen
(O2) %
Natural Gas Analysis 11/17/2025 94 0 0 6 0

Incident Materials

Cause Source Material Volume Units
Unk. Released Recovered Lost
High Line Pressure Gas Compressor Station Natural Gas Vented 813 0 813 Mcf
 
The concentration of dissolved chloride in the produced water >10,000 mg/l:           Yes           No        

Incident Events

Date Detail
11/17/2025 Corrective actions provided by the operator: the leaking suction valve was fixed to prevent compressor to pressure up. Rupture disc operated by design to relive high pressure.
11/17/2025 Primary Equipment identified by the operator (Gas Compressor Station, with additional details: Compressors at 32-7 went shut down on high discharge pressure, the suction control valve closed but leaked by causing rupture disc to pop off.)
11/17/2025 Steps taken to prevent waste provided by the operator: Mechanic found the issue and shut in manual block valve to stop the release
11/17/2025 Incident updated by the operator, upon the submission of a amendment for venting of natural gas report.
11/17/2025 The (11/17/2025, C-129A) application [527046] was assigned to this incident.
11/07/2025 The (11/07/2025, NOMVF) application [524541] was assigned to this incident.
11/07/2025 New incident created by the operator, upon the submission of a notification of venting or flaring.
11/06/2025 The event discovered by the operator; will be tracked as a Flare till submission of the required subsequent C-129A.

Incident Severity
Major release as defined by 19.15.29.7(A) NMAC?
Yes No

Incident Corrective Actions






Orders No Orders Found